LT Power Cable Sizing, Derating & Voltage Drop Sizing Engine

Accurately calculate derated current capacity, percentage voltage loss across long runs, and optimum cross-sectional conductors for power and lighting sub-feeders.

IS:7098 Part 1 • IS:1554 • BS:7671

LT Power Cable Sizing & Voltage Drop Sizing Engine

Computes cable ampacity derating, route voltage drop percentage, and cross-section requirements conforming to Indian Electricity Rules.

✓ Vd 2.46% ≤ 5% Limit
150 kW
Full Load: 245.5 Amps
110 m
Recommended Cable Specification
Optimum Cross-Sectional Size
3.5C × 185 mm²
1.1 kV XLPE Insulated, Galvanized Steel Armoured (Aluminium)
Voltage Drop Percentage2.46%Passes (≤ 5%)
Absolute Voltage Loss10.2 VoltsTerminal: 404.8 V
Total Derating Multiplier0.85At 45°C + grouping
Per-Run Current Demand246 AmpsOf 246 A total
Calculation Method (IS:7098):
ΔV = √3 × 245.5A × 110m × (0.211×0.85 + 0.074×0.53)/1000 = 10.2 V
Send Cable Sizing to WhatsApp →
Indian Standards Specification

Cable Sizing & Permissible Voltage Drops

Statutory compliance thresholds mandated by the Central Electricity Authority (CEA) and BS:7671.

3.0% Limit for Lighting Feeders

Excessive voltage drop in lighting circuits leads to luminaire flickering, LED driver overheating, and premature lamp failure. Maximum permissible drop is strictly 3.0%.

5.0% Limit for Power & Motor Feeders

For motor circuits and general power distribution, total steady-state drop from transformer terminal to equipment load terminal shall not exceed 5.0% to ensure rated motor torque.

Thermal Derating in Delhi NCR Summers

IS:7098 tables assume 40°C in air. In Delhi NCR, summer temperatures frequently reach 45°C–48°C. A thermal derating multiplier of 0.88 to 0.90 must always be factored in.