Clean Agent Gas Suppression Sizing Engine (FM-200 / Novec 1230)
Accurately size extinguishing agent mass, seamless cylinder quantities, manifold pipe headers, and structural pressure relief damper (PRD) venting for mission-critical IT facilities.
Clean Agent Installation Guidelines
Essential room sealing, abort switch, and discharge protocols under NFPA 2001.
NFPA 2001 mandates that 95% of the design concentration must be achieved within 10 seconds of release to rapidly extinguish energized electrical fires before thermal runaway occurs.
During rapid gas flooding, positive pressure builds up instantly. Gravity or motorized PRD dampers are mandatory on external walls to prevent gypsum partition blow-outs and structural damage.
The enclosure must hold the extinguishing gas concentration for a minimum 10-minute hold time. All cable penetrations and pipe sleeves must be fire-stopped with certified sealant.