HT/LT Substation Transformer, Diversity & DG Sizing Engine
Accurately size 11kV/433V step-down transformers, full-load amps, fault level capacity, and secondary Air Circuit Breakers (ACB) based on empirical diversity factors.
Substation Engineering Standards
Central Electricity Authority (CEA) norms and Indian Standard specifications.
Not all connected loads operate simultaneously. CPWD guidelines mandate diversity factors between 0.70 and 0.80 for commercial IT buildings to avoid expensive over-sizing of transformers.
IS:2026 specifies %Z typically at 4.75% to 5.0% for transformers up to 1000 kVA, and 6.25% for 1250 kVA and above, determining the symmetrical short-circuit current that switchgear must withstand.
When sizing diesel generators, ensure the engine can take a minimum 60% block step load when large chiller motors or fire pumps start up without suffering voltage dip beyond 15%.