Water Sump, Domestic Demand & Booster Pump Sizing Engine

Accurately size raw water underground sumps, treated flushing tanks, dedicated fire reservoirs, and VFD-driven hydro-pneumatic booster pumping sets for multi-storey buildings.

NBC 2016 Vol. 2 Part 9 • CPWD Manual

Water Sump, Domestic Demand & Booster Pump Sizing Engine

Computes statutory per capita water demands, underground/overhead tank storage split, and hydro-pneumatic booster pumping head.

Daily Demand: 27.0 KL/day

Standard commercial office with canteen and executive rest bays.

600 Persons
30 Meters (~9 Floors)
Tank & Booster Pump Sizing
Total Underground Water Sump Complex
177 KL Storage
15 KL Domestic + 12 KL Flushing + 150 KL Dedicated Fire Static Sump
Overhead Tank (OHT) Size11 KL OHT6 KL Dom + 5 KL Flush
Hydro-Pneumatic Flow113 LPM (6.8 m³/h)Peak instantaneous discharge
Total Dynamic Head (TDH)55 m (5.4 Bar)With 1.5 Bar at topmost tap
Booster Pump Set & Tank2W + 1S (2 kW)With 200L Pressure Vessel
NBC 2016 Part 9 Water Balance:
Total Daily = 600 × 45 = 27,000 L/day (27.0 KLD)
Send Water Sump Scope to WhatsApp →
Plumbing Standards

Public Health Engineering (PHE) Design Principles

Statutory water conservation and dual-piping requirements under NBC 2016 Part 9.

Dual-Piping Flushing Mandate

All commercial and large residential townships in Delhi NCR must incorporate dual-piping to utilize 100% recycled STP treated water for toilet flushing and cooling tower make-up.

Independent Fire Water Sump

Fire water static reserves (100–250 KL) must be physically partitioned from domestic water or connected with high-level overflows so domestic pumps cannot deplete fire suction reserves.

Terminal Pressure at Taps

To avoid user dissatisfaction and ensure automatic sensor flush valves operate smoothly, booster systems must maintain a minimum terminal residual pressure of 1.5 kg/cm² (15m head) at the topmost floor.